Calc Resistance of 1300ft 6AWG Copper Wire at 45°C
To calculate the resistance of a 1300 ft, 6 AWG copper wire at 45°C, we'll use the formula for resistance: R = ρL/A, where R is the resistance, ρ (rho) is the resistivity, L is the length, and A is the cross-sectional area. First, let's find the suitable values for ρ and A.
The resistivity of copper at 45°C can be approximated using the temperature coefficient of resistivity (TCR) of copper (0.393%/°C).
Copper Resistivity at 45°C
At 20°C, the resistivity of copper is approximately 1.68×10-8 Ω·m. Using TCR, we can find the resistivity at 45°C:
ρ = (1 + TCR * ΔT) * ρ0
Where ρ0 is the resistivity at 0°C, TCR is the temperature coefficient, and ΔT is the temperature difference. Plugging in the values, we get:
Resistivity Calculation
ρ = (1 + 0.00393 * (45 - 20)) * 1.68 * 10-8
ρ ≈ 1.92 * 10-8 Ω·m
Copper Wire Cross-Sectional Area
The cross-sectional area (A) of a 6 AWG copper wire can be found using the AWG-to-diameter table. A 6 AWG copper wire has a diameter (D) of approximately 0.128 inches.
The cross-sectional area is then A = π * (D/2)2.
Cross-Sectional Area Calculation
A = π * (0.128 / 2)2
A ≈ 0.0002217 m2
Now that we have ρ and A, we can calculate the resistance (R).
Calculating the Resistance
The length (L) of the wire is 1300 ft, which is equivalent to 396.24 m. Plugging in the values, we get:
R = (ρL) / A
R = (1.92 * 10-8 * 396.24) / 0.0002217
R ≈ 3.18 Ω
So, the resistance of a 1300 ft, 6 AWG copper wire at 45°C is approximately 3.18 ohms. Keep in mind that this is a simplified calculation and doesn't account for factors like magnetic effects and frequency dependence. Always use accurate measurement for precise results.